Impact Factor:5.967
DOI number:10.1109/TPEL.2021.3061624
Journal:IEEE Transactions on Power Electronics
Key Words:Asymmetric system, grid-tied converter, impedance model (IM), stability margin, transfer matrices.
Abstract:Frequency responses are nonidentical between the positive and the negative frequency range for symmetric three-phase systems modeled with complex transfer functions, which shows unbalanced stability margins. The unbalanced stability margins limit the system performance, as the system dynamics are restricted by the worst one. This article extends the discussion of
unbalanced stability margins to asymmetric three-phase systems,
i.e., three-phase grid-tied inverters, which are described by transfer matrices. The reason for unbalanced stability margins is analytically investigated, and different impacts are analyzed. It is found that both the control delay and asymmetric control loops can lead to the unbalanced stability margins. To improve the performance limited by the worst stability margin, a margin balancing control is proposed. By implementing a phase correction term, the worst stability margin can be increased by reducing the best one. As a result, the overall stability margin of the system can be improved. The design procedure is elaborated based on a 2-MW inverter system. Verifications are presented based on a 1-kW prototype including simulations, experimental results, and Nyquist analyses. This method applies to all types of grid-tied inverters with multiple control loops.
Indexed by:Journal paper
Discipline:Engineering
Document Type:J
Volume:36
Issue:9
Page Number:10716-10728
ISSN No.:0885-8993
Translation or Not:no
Date of Publication:2021-02-23
Included Journals:SCI
Links to published journals:https://ieeexplore.ieee.org/xpl/RecentIssue.jsp?punumber=63